| Conductors: |
annealed copper conducter, circular
compacted or shaped stranded class 2 acc. to |
| Insulation: |
cross-linked polyethylene XLPE type
GP8 acc. to BS 7655-1.3 |
| Bedding: |
PVC compound |
| Armour: |
for single-core cables -single layer
of aluminium wires applied spirally over the bedding (AWA)
for two or more cores cables - single
layer of galvanized steel wires applied spirally over the |
| Outer sheath: |
black PVC compound Type 9 acc. to BS
7655-4.2 |
| Core Identification: |
1-core: red or black
2-core: red, black
3 -core: red, yellow, blue
4 -core: red, yellow, blue, black
5-core: red, yellow, blue, black
auxiliary cables: green/yellow white with black numbering |
| Maximum conductor operating
temperature: |
+90°C |
| Lowest installation temperature: |
0°C |
| Maximum short-circuit conductor
temperature: |
+250°C |
| Minimum bending radius: |
6 x D for cables with circular copper
conductors and 8 x D for cables with shaped copper conductors;
D - overall diameter of the cable. |
| Application: |
For use in fixed installations in industrial
areas, buildings and similar applications. |